Main menu:
products > pipe isolations as per DIN 1988
Winco mixer units for the automatic mixing and dispensing of a ready-to-use disinfectant,
using disinfectant concentrate and tap water.
Important information:
DIN 1988, part 4 from December 1988 "technical norms for drinking water
installations (TRWI), class disinfectant solutions into category 4.
Units of category 4 have to have safety lugs for the cover of drinking water:
here it is a mains isolator with a pipe isolation as assembly of type 2.
To be set in: industry, swimming-pools, sport facilities, saunas, and laundries.
Mixing rate: | variable setting from 0.1% to 3.0% |
Safeties: | - cover of the drinking water by pipe isolation - shut-off should the concentrate box become empty - separation of media between concentration and tap water by a specially formed membrane of EPDM |
Construction: | - water pressure 8.0 bar max. - 2.0 bar min. - mixing rate: variable from 0.1% to 3.0% - robust, easy to maintain and operate - solution can be adjusted to suit most commercially available water miscible disinfectant concentrates |
D010110 |
Universal Mixer Units Winco ZM 3 UE Operating principle: pressure system. Output settings: ZM 3 UE Concentrate level = variable setting from 0.1 % - 3.0 % Concentrate tank capacity: 3 liters Automatically shut-off: the unit will switch itself off should the concentrate tank become empty, (avoiding the risk of inadvertently using clean tap water for "disinfecting"). Operational Data: Connectors: Inlet and outlet = R 1/2". Chrome-plated MS union nut. Water pressure: 8.0 bar max., 2.0 bar min., maximum water temperature: 45 °C max., flow rate: 1000l/h at 4 bar, separation of the media in the mixer unit by means of a special membrane made from EPDM and 1.4301 stainless steel. Dimensions: Height approx. 350 mm; width (outer sealing face) approx. 210 mm. Weight: 5 kg approx. (ZM 3 UE) Important note: As in DIN 1988, part 4, December 1988, safety combinations, back-flow-preventer, pipe aeration, for disinfectant equipment are no more allowed. Therefore the pipe isolator EA 2 type Winco VNT 800 has been developed for you. |
D010151 | Pipe isolation to cover drinking water as per DIN 1988, part 4, "Technical Norms for Drinking Water Installations" (TRWI) type Winco VNT 800 In general consisting of: . Grounded stainless-steel box, material no. 1,4301 with a frontal opening door . Pipe isolator electronically controlled on EA 2, DVGW license no 569 . Magnetic valve as a reserving valve, material no. MS 58 . On/off switch and signal lamp "Operation" green Connectors: Tap water inlet: R ½" outside threat Tap water outlet: R ½" outside threat Tickling water Connector: R 1", plastic adhesive couple ELT: 230V, 50 Hz, 3 x 1.5² Dimension: 300 x 380 x 155 mm Weight: approx. 11 kg (VNT 800) Terms of delivery: ex work, exclusive packing Delivery period: approx. 2 weeks Terms of payment: 14 days 2% discount, 30 days net |
D900010 | Commissioning and operator training should be carried out by LSK-Wintrich engineers. Guarantee as per LSK-Wintrich general terms and conditions. Fitting and connection are not included in the price of the product. Maintenance contract as requested. Note: Please fit a sampling valve in the outlet line behind the mixer (e. g. item D010530, R ½", chromed)! |